Schneider A9D10820 IC60H RCBO 1PPNS 20A Type C 10MA Curve A 230V
A9D10820
iC60H Earth Leakage Circuit Breaker - 1P+N - C Curve -20A - 10mA - 240V
The Acti9 iC60H is a high-performance modular residual current breaker with overcurrent protection (RCBO). Designed for residential, commercial, and industrial applications, it provides reliable protection against short circuits, overloads, and earth leakage faults. Its advanced safety features ensure fast response and long-lasting performance.
- Residual Current and Overcurrent Protection: Combines short-circuit, overload, and earth leakage protection in a single device.
- 1P+Ns Configuration: Provides 1 protected pole with neutral switching for enhanced safety.
- Type A Earth Leakage Protection: Detects both AC and pulsating DC residual currents.
- 10mA Sensitivity: Ideal for high-sensitivity applications requiring immediate fault detection.
- Instantaneous Earth Leakage Protection Delay: Ensures rapid disconnection during fault conditions.
- High Short Circuit Breaking Capacity: Rated up to 10,000A as per IEC 61009-2-2.
- VisiTrip Indicator: Reduces intervention time by highlighting the faulty circuit.
- VisiSafe Green Strip: Guarantees physical opening of contacts for safe downstream maintenance.
- Fast Closing Mechanism: Enhances service life with operation independent of manual force.
- Long-Lasting Durability:
- Electrical Endurance: Up to 5,000 cycles.
- Mechanical Endurance: Up to 20,000 cycles.
- Compact DIN Rail Mountable Design: Saves space while providing efficient protection.
Technical Specifications
- Poles: 1P+Ns (single-pole with neutral switching).
- Rated Current:20A.
- Tripping Curve: C curve.
- Residual Current Sensitivity: 10mA.
- Earth Leakage Protection Type: Type A.
- Rated Short Circuit Capacity (Icn): 10,000A (IEC 61009-2-2).
- Operational Voltage (Ue): 240VAC.
- Insulation Voltage (Ui): 400VAC.
- Impulse Withstand Voltage (Uimp): 4kV.
- Frequency: 50Hz.
- Mounting: DIN rail installation.
- Width: 2 pitches of 9mm.
- Dimensions: 18mm (W) x 110mm (H) x 77.5mm (D).
- Weight: 205g.
- Protection Rating:
- IP20 (as per IEC/EN 60529).
- IP40 when installed in a modular enclosure.
- Standards Compliance: BS EN 61009-1, AS/NZS 61009.1.
- Operating Temperature: -15°C to 60°C.
- Storage Temperature: -40°C to 85°C.
✅ The Acti9 iC60H Earth Leakage Circuit Breaker offers superior electrical protection with high sensitivity, quick fault detection, and robust design, making it a perfect choice for residential and industrial installations.

Range | Schneider Acti 9 |
Trip Type | C Curve Type A |
Product | RCBO |
Type | Singe Pole + Plug on Neutral |
Current Rating | 20A |
Delivery Costs
Our standard delivery charge to UK mainland addresses is £5.90 ex-VAT.
Take advantage of FREE* Delivery when you spend over £100 (per order) ex-VAT.
*Delivery charges to JE, GY, TR, BT, IM, IV, HS, KW, ZE and certain PA post codes are £12.00 ex-VAT.
Solar Panels, Batteries and Inverters
Due to their size all solar panels, batteries and inverters orders up to 50 qty will be despatched on a pallet and incur a £120** ex-VAT delivery charge.
**£180 ex VAT to JE, GY, TR, BT, IM, IV, HS, KW, ZE and certain PA post codes.
Click here to find out more.